Definitions...

Approved : Accepted or acceptable under an applicable specification stated or cited in these rules, or accepted as suitable for the proposed use by the authority.
Area drain : A drain installed to collect surface or storm water from an open area of a building or property.
Building drain : Is that part of the lowest horizontal piping of a house drainage system which receives the discharge from soil, waste, and other drainage pipes inside the walls of any building and conveys the same to the building sewer.
Building sewer : Is that part of the horizontal piping from the building wall to its connection with the main sewer or the primary treatment portion of an on-site wastewater treatment and disposal system conveying the drainage of one building site.
Chamber system : Is a buried structure, typically with a domed or arched top, providing at least a six-inch height of side wall soil exposure, creating a covered open space above a buried soil infiltrative surface.
Conventional : When used in reference to sewage treatment means a soil absorption system involving a series of two foot wide trenches filled -with gravel one foot deep, containing a four inch diameter rigid pipe to convey the sewage effluent.
Distribution box : Is a structure designed to accomplish the equal distribution of wastewater to two or more soil absorption trenches.
Drainage ditch : Is any watercourse meeting the classification of a general use segment, which includes intermittent watercourses and those watercourses which typically flow only for short periods of time following precipitation in the immediate locality and whose channels are normally above the water table.
Drip irrigation : Is a form of subsurface soil absorption using shallow pressure distribution with low-pressure drip emitters.
Drop box : Is a structure to divert wastewater flow into a soil absorption trench until the trench is filled to a set level, then allow any additional waste, which is not absorbed by that trench, to flow to the next drop box or soil absorption trench.
Dwelling : Means any house or place used or intended to be used by humans as a place of residence.
Fill soil : Means clean soil, free of debris or large organic material, which has been mechanically moved onto a site and has been in place for less than one year.
Foundation drain : Means that portion of a building drainage system provided to drain groundwater from the outside of the foundation or over or under the basement floor not including any wastewater and not connected to the building drain.
Free access filter (open filter) : Means an intermittent sand filter constructed within the natural soil or above the ground surface with access to the distributor pipes and top of the filter media for maintenance and media replacement.
Gravel : Means stone screened from river sand or quarried. Concrete aggregate designated as Class II by the department of transportation is acceptable.
Gravelless pipe system : Means an absorption system comprised of large diameter (8 and 10 inches) corrugated plastic pipe, perforated with holes on a 120-degree arc centered on the bottom, wrapped in a sheath of geo-textile filter wrap and installed level in a trench without gravel bedding or -cover.
Individual mechanical aerobic wastewater treatment system : Means an individual wastewater treatment and disposal system employing bacterial action -which is maintained by the utilization of air or oxygen and includes the aeration plant and equipment and the method of final effluent disposal.
Intermittent sand filters : Are beds of granular materials 24 to 36 inches deep underlain by graded gravel and collecting tile. Wastewater is applied intermittently to the surface of the bed through distribution pipes or troughs and the bed is underdrained to collect and discharge the final effluent. Uniform distribution is normally obtained by dosing so as to flood the entire surface of the bed. Filters may be designed to provide free access (open filters), or may be buried in the ground (buried filters or subsurface sand filters).
Lake : Means a natural or man-made impoundment of water with more than one acre of water surface area at the high water level.
Limiting layer : Means bedrock, seasonally high groundwater level, or any layer of soil with a stabilized percolation rate exceeding 60 minutes for the water to fall one inch.
Mound system : Is an alternative above-ground system used to absorb effluents from septic tanks in cases where either seasonally high water table, high bedrock conditions, slowly permeable soils or limited land areas prevent conventional subsurface absorption systems.
On-site wastewater treatment and disposal system : Means all -equipment and devices necessary for proper conduction, collection, storage, treatment, and disposal of wastewater from four or fewer dwelling units or other facility serving the equivalent of 15 persons (1,500 gpd) or less. This includes domestic waste whether residential or nonresidential but does not include industrial waste of any flow rate. Included within the scope of this definition are building sewers, septic tanks, subsurface absorption systems, mound systems, sand filters, constructed wetlands and individual mechanical/aerobic wastewater treatment systems.
Percolation test : Is a falling water level procedure used to determine the ability of soils to absorb primary treated wastewater.
Pond : Means a man-made impoundment of water with a water surface area of one acre or less at the high water level.
Primary treatment : Is a unit or system to separate the floating and settleable solids from the wastewater before the partially treated effluent is discharged for secondary treatment.
Professional soil analysis : Is an alternative to the percolation test which depends upon a knowledgeable person evaluating the soil factors, such as color, texture, and structure, in order to determine an equivalent percolation rate. Demonstrated training and experience in soil morphology (testing absorption qualities of soil by the physical examination of the soil's color, mottling, texture, structure, topography and hillslope position) shall be required to perform a professional soil analysis.
Roof drain : A drain installed to receive water collecting on the surface of a roof and discharging into an area or storm drain system.
Secondary treatment system : Is a system which provides biological treatment of the effluent from septic tanks or other primary treatment units to meet minimum effluent standards. Examples include soil absorption systems, sand filters, mechanical/aerobic systems, or other systems providing equivalent treatment.
Septage : Means the liquid contents (including sludge and scum) of a septic tank normally pumped out periodically and transported to another site for disposal.
Septic tank : Is a watertight structure into which wastewater is discharged for solids separation and digestion, referred to as part of the closed portion of the treatment system.
Sewage wastewater : Is the water-carried waste derived from ordinary living processes.
Sludge : Means the digested or partially digested solid material accumulated in a wastewater treatment facility.
Stream : Means any watercourse listed as being a designated use segment, which includes any watercourse which maintains flow throughout the year, or contains sufficient pooled areas during intermittent flow periods to maintain a viable aquatic community of significance.
Subsurface absorption system : Is a system of perforated conduits connected to a distribution system, forming a series of subsurface, water-carrying channels into which the primary treated effluent is discharged for direct absorption into the soil (referred to as part of the open portion of the treatment system).
Subsurface sand filter : Is a system in which the effluent from the primary treatment unit is discharged into perforated pipes, filtered through a layer of sand, and collected by lower perforated pipes for discharge to the surface or to a subsurface absorption system. A subsurface sand filter is an intermittent sand filter which is placed within the ground and provided with a natural topsoil cover over the crown of the distribution pipes.
Wastewater management district : Means an entity organized in accordance with permitting legislation to perform various specific functions such as planning, financing, construction, supervision, repair, maintenance, operation and management of on-site wastewater treatment and disposal systems within a designated area.

General Regulations...

Connections to approved sewer system : (1) No on-site wastewater treatment and disposal system shall be installed, repaired, or rehabilitated where a public sanitary sewer is available or where a local ordinance requires connection to a public system. The public sewer may be considered as not available when such public sewer or any building or any exterior drainage facility connected thereto, is located more than two hundred feet from any proposed building or exterior drainage facility on any lot or premises which abuts and is served by such public sewer. Final determination of availability shall be made by the administrative authority. (2) When a public sanitary sewer becomes available within two hundred feet, any building then served by an on-site wastewater treatment and disposal system shall connect to said public sanitary sewer within a time frame or under conditions set by the administrative authority. (3) When a public sanitary sewer is not available, every building wherein persons reside, congregate or are employed shall be provided with an approved on-site wastewater treatment and disposal system. (4) If a building is to be connected to an existing on-site wastewater treatment and disposal system, that existing system shall meet the standards of these rules and be appropriately sized.
Discharge restrictions : It is prohibited to discharge any wastewater from onsite wastewater treatment and disposal systems (except under an NPDES permit) to any ditch, stream, pond, lake, natural or artificial waterway, county drain tile, surface water drain tile, land drain tile or to the surface of the ground. Under no conditions shall effluent from on-site wastewater treatment and disposal systems be discharged to any abandoned well, agricultural drainage-wer or sinkhole. Existing discharges to any of the above-listed locations or structures shall be eliminated by constructing a system which is in compliance with the requirements of these rules.
Construction or alteration : All on-site wastewater treatment and disposal systems constructed or altered after the effective date of these rules shall comply with these requirements. Alteration includes any changes that effect the treatment or disposal of the waste. Repair of existing components that does not change the treatment or disposal would be exempt. However, the discharge restrictions in b above would always apply.

Site Analysis...

Site evaluation : A site evaluation shall be conducted prior to issuance of a construction permit. Consideration shall be given, but not be limited to, the impact of the following: topography; drainageways; terraces; floodplain; percent of land slope; location of property lines; location of easements; buried utilities; existing and proposed tile lines; existing, proposed and abandoned water wells; amount of available area for the installation of the system; evidence of unstable ground; alteration (cutting, filling, compacting) of existing soil profile; and soil factors determined from a soil analysis, percolation tests and soil survey maps if available.
Soil survey reports : During a site analysis and investigation, maximum use should be made of soil survey reports which are available from USDA Natural Resources Conservation Service. A general identification of the percolation potential can be made from soil map units in Iowa. Verification of the soil permeability on the specific site must be performed.

Minimum Distances...

All on-site wastewater treatment and disposal systems shall be located in accordance with the minimum distances shown in table given below.

Minimum Distance in Feet From Closed Portion of Treatment System (1) Open Portion of Treatment System (2)
Private water supply well 50' 100'
Public water supply well 200' 200'
Groundwater heat pump borehole 50' 100'
Lake or reservoir 50' 100'
Stream or pond 25' 25'
Edge of drainage ditch 10' 10'
Dwelling or other structure 10' 10'
Property lines (unless a mutual easement is signed and recorded) 10' 10'
Other type subsurface treatment system 5' 10'
Water lines continually under pressure 10' 10'
Suction water lines 50' 100'
Foundation drains or subsurface tiles 10' 10'
(1) Includes septic tanks, mechanical aeration tanks and impervious vault toilets.
(2) Includes subsurface absorption systems, mound systems, intermittent sand filters, constructed wetlands or waste stabilization ponds.

Building Sewers...

Location and Construction...

The types of construction and distances as shown in table given below shall be maintained for the protection of water supplies. The distances shall be considered minimum and increased where possible to provide better protection.

Sewer construction Distance from well water supply
Private Public
1. Schedule 40 plastic pipe with approved type joints or cast-iron soil pipe (extra heavy or centrifugally cast) with joints of preformed gaskets 10 25
2. Sewer pipe installed to remain watertight and root-proof 50 75

Requirements for Building Sewers...

Type : Building sewers used to conduct wastewater from a building to the primary treatment unit of an on-site wastewater treatment and disposal system shall be constructed of Schedule 40 plastic pipe (or SDR 26 or stronger) with solvent-weld or bell-and-gasket type joints, or cast iron with integral bell-and-gasket type joints.
Size : Such building sewers shall not be less than 4 inches in diameter.
Grade : Such building sewers shall be laid to the following minimum grades ; (a) 4 - inch sewer = 12 inches per 100 feet, (b) 6 - inch sewer = 8 inches per 100 feet.

Clean - Outs...

Spacing : A cleanout shall be provided where the building sewer leaves the house and at least every 100 feet allowing rodding downstream.
Change of direction : An accessible cleanout shall be provided at each change in direction or grade, if the change exceeds 45 degrees.

Primary Treatment - Septic Tanks...

General Requirements...

Septic tank required : Every on-site wastewater treatment and disposal system except mechanical-aerobic systems, shall have as a primary treatment unit a septic tank as described in this rule. All wastewater from the facility serviced shall discharge into the septic tank.
Easements : No septic tank shall be located upon property under ownership different from the ownership of that property or lot upon which the wastewater originates unless easements to that effect are legally recorded and approved by the proper administrative authority.
Effluent discharge requirements : All septic tank effluent shall discharge into a secondary treatment system in compliance with this rule or other system approved by the administrative authority.
Prohibited wastes : Septic tanks shall not be used for the disposal of chemical wastes or grease in quantities which might be detrimental to the bacterial action in the tank or for the disposal of drainage from roof drains, foundation drains, or area drains.

Capacity...

Minimum capacity : The minimum liquid holding capacity shall be as specified in the following table (capacity may be obtained by using one or more tanks) ; (a) up to and including 3 - bedroom homes = 1,000 gal, (b) 4 - bedroom homes = 1,250 gal, (c) 5 - bedroom homes = 1,500 gal, (d) 6 - bedroom homes = 1,750 gal.
Two hundred fifty gallons of capacity shall be added to each of these tank volumes if a kitchen garbage disposal unit, water softener, or a high volume water use fixture such as a whirlpool bath is to be used.
Other domestic waste systems : In the event that any installation serves more than a 6 - bedroom home or its equivalent, or serves a facility other than a house and serves the equivalent of 15 persons or less (1,500 gal / day), approval of septic tank capacity and design must be obtained from the administrative authority. Minimum septic tank liquid holding volume shall be two times the estimated daily sewage flow.
Minimum depth : Minimum liquid holding depth in any compartment shall be 40 inches.
Maximum depth : Maximum liquid holding depth for calculating capacity of the tank shall not exceed 61/2feet.
Dimensions : The interior length of a septic tank should not be less than 5 feet and shall be at least 1½ times the width (larger length-to-width ratios are preferred). No tank or compartment shall have an inside width of less than 2 feet. The minimum inside diameter of a vertical cylindrical septic tank shall be 5 feet.

Construction Details...

Fill soil : Any septic tank placed in fill soil shall be placed upon a level, stable base that will not settle.
Compartmentalization : Every septic tank shall be divided into two compartments as follows (compartmentalization may be obtained by using more than one tank) ; (1) The capacity of the influent compartment shall not be less than one-half nor more than two-thirds of the total tank capacity, (2) The capacity of the effluent compartment shall not be less than one-third nor more than one-half of the total tank capacity.
Inlet / outlet : The invert of the inlet pipe shall be a minimum of 2 inches and a maximum of 4 inches higher than the invert of the outlet pipe.
Baffles : Four-inch diameter schedule 40 plastic pipe tees shall be used as inlet and outlet baffles. Inlet tees shall extend at least 6 inches above and 8 inches below the liquid level of the tank. The inlet tee shall extend below the liquid level no more than 20 percent of the liquid depth. The outlet tee shall extend above the liquid level a distance of at least 6 inches and below the liquid level a distance of at least 10 inches but no more than 25 percent of the liquid depth. A minimum clearance between the top of the inlet and outlet tees and the bottom of the tank lid of 2 inches shall be provided. A horizontal separation of at least 36 inches shall be provided between the inlet baffle and the outlet baffle in each compartment. A horizontal slot 4 inches by 6 inches, or two suitably spaced 4-inch diameter holes in the tank partition, may be used instead of a tee or baffle, the top of the slot or holes to be located below the water level a distance of one-third the liquid depth. A ventilation hole or slot shall be provided in the partition, at least 8 itches above the liquid level.
Access : Access must be provided to all parts of septic tanks necessary for adequate inspection, operation, and maintenance. An access opening shall be provided at each end of the tank over the inlet and outlet. These openings shall be at least 18 inches in the smallest dimension if the tank has no other openings. Alternatively, a single opening at least 24 inches in diameter may be provided at the center of the tank allowing access to both compartments, with two smaller openings at least 6 inches in diameter over both inlet and outlet. If the top of the tank is to be greater than 12 inches below the finished ground surface, a riser at least 24 inches in diameter must be installed over each manhole of 18 inches in diameter or more to bring the top of the manhole Ed to within 6 inches of the finished ground surface.

Construction...

Materials : Tanks shall be constructed of poured concrete or plastic resistant to corrosion or decay and designed so that they will not collapse, or rupture when subjected to anticipated earth and hydrostatic pressures when the tanks are either full or empty. Metal tanks are prohibited.
Dividers : Tank divider walls and divider wall supports shall be constructed of heavy, durable plastic, fiberglass, concrete or other similar corrosion-resistant materials approved by the administrative authority.
Inlet and outlet ports : Inlet and outlet ports of pipe shall be constructed of heavy, durable schedule 40 PVC plastic sanitary tees or other similar approved corrosion resistant material.

Wall Thickness...

Minimum wall thickness for tanks shall conform to the following specifications ; (1) Poured concrete = 6 inches thick, (2) Poured concrete, reinforced = 4 inches thick, (3) Special concrete mix, vibrated and reinforced = 2.5 inches thick, (4) Fiberglass or plastic = 25 inches thick.

Concrete Specifications...

Concrete used in precast septic tank construction shall have a maximum water-to-cement ratio of 0.45. Cement content shall be at least 650 pounds per cubic yard. Minimum compressive strength (f'c) shall be 4,000 psi (28 Mpa) at 28 days of age. The use of ASTM C150 Type II cement or the addition of silica fume or Class F fly ash is recommended.

Tank Bottoms...

Septic tank bottoms shall conform to the specifications set forth for septic tank walls except special mix concrete shall be at least 3 inches thick.

Tank Tops...

Concrete or masonry septic tank tops shall be a minimum of 4 inches in thickness and reinforced with 3/8-inch reinforcing rods in a 6-inch grid or equivalent. Fiberglass or plastic tank tops shall be a minimum of ¼ inch in thickness and shall have reinforcing and be of ribbed construction.

Reinforcing Steel Placement...

The concrete cover for reinforcing bars, mats, or fabric shall 'not be less than 1 inch.

Bedding...

Fiberglass or plastic tanks shall be bedded according to manufacturer's specifications. Provisions should be made to prevent flotation when the tanks are empty.

Connecting Pipes...

Minimum diameter : The pipes connecting septic tanks installed in series and at least the first 5 feet on the effluent side of the last tank shall be a minimum of 4-inch diameter schedule 40 plastic.
Tank connections : All inlet and outlet connections at the septic tanks shall be made by self-sealing gaskets cast into the concrete or formed into the plastic or fiberglass.
Joints : All joints in connecting schedule 40 plastic pipe shall be approved plastic pipe connections such as solvent welded or compression-type gaskets.
Pipe in unstable ground : Schedule 40 plastic pipe shall be used extending across excavations on unstable ground to at least 2 feet beyond the point where the original ground has not been disturbed in septic tank installations. If the excavation spanned is more than 2 feet, it must be filled with sand or compacted fill to provide a firm bed for the pipe. The first 12 inches of backfill over the pipe shall be applied in thin layers using material free from stones, boulders, large frozen chunks of earth or any similar material that would damage or break the pipe.

Secondary Treatment - Subsurface Absorption Systems...

General Requirements...

Locations : All subsurface absorption systems shall be located on the property to maximize the vertical separation distance from the bottom of the absorption trench to the seasonal high groundwater level, bedrock, hardpan or other confining layer, but under no circumstances shall this vertical separation be less than 3 feet.
Soil evaluation : A percolation test or professional soil analysis is required before any soil absorption system is installed. (a) Percolation test : The percolation test procedure is outlined before, (b) Alternative analysis : If a professional soil analysis is performed, soil factors such as soil content, color, texture, and structure shall be used to determine a percolation rate, (c) Acceptable percolation rate : An area is deemed suitable for conventional soil absorption if the average percolation test rate is 60 minutes per inch or less and greater than 1 minute per inch. However, if an alternative type system is proposed (e.g., mound), then the percolation test should be extended to determine whether a percolation rate of 120 minutes per inch is achieved, (d) Confining layer determination : An additional test hole 6 feet in depth or to rock, whichever occurs first, shall be provided in the center of the proposed absorption area to determine the location of groundwater, rock formations or other confining layers. This 6-foot test hole may be augured the same size as the percolation test holes or may be made with a soil probe.
Groundwater : If seasonal high groundwater level is present within 3 feet of the trench bottom final grade and cannot be successfully lowered by subsurface tfle drainage, the area shall be classified as unsuitable for the installation of a standard subsurface absorption system. Consult the administrative authority for an acceptable alternative method of wastewater treatment.
Site limitations : In situations where specific location or site characteristics would appear to prohibit normal installation of a soil absorption system, design modifications may be approved by the administrative authority which could overcome such limitations. Examples of such modifications could be the installation of subsurface drainage, use of shallow or at-grade trenches, use of dual soil treatment areas, mound system or water conservation plans.
Prohibited drainage : Roof, foundation and storm drains shall not discharge into or upon subsurface absorption systems. Nothing shall enter the subsurface absorption system which does not first pass through the septic tank.
Prohibited construction : There shall be no construction of any kind, including driveways, covering the septic tank, distribution box or absorption field of an on-site wastewater treatment and disposal system. Vehicle access should be infrequent, primarily limited to vegetation, maintenance.
Driveway crossings : Connecting lines under driveways shall be constructed of schedule 40 plastic pipe or equivalent, and shall be protected from freezing.
Easements : No wastewater shall be discharged upon any property under ownership different from the ownership of the property or lot upon which it originates unless easements to that effect are legally recorded and approved by the administrative authority.

Trench Length Requirements...

Percolation charts : Tables given below specify lineal feet of lateral trenches required in accordance with the results of the standard percolation tests. Tables list optional methods for determining length of lateral trenches or sizing of absorption beds. The alternative option for increased rock usage shall be used only when the size of lots limits the use of trench lengths prescribed in the tables. Absorption beds shall not be used except when the lot size limitations preclude the installation of a lateral trench system. Further details concerning limitations of these two alternatives should be obtained from the administrative authority prior to requesting authorization for installation.
Unsuitable absorption : Conventional subsurface soil absorption trenches shall not be installed in soils that have a percolation rate less than 1 minute per inch or greater than 60 minutes per inch. Plans for an alternative method of wastewater treatment shall be submitted to the administrative authority for approval prior to construction.

Min. Per inch 2-bedroom
300 gal / day
3-bedroom
450 gal / day
4-bedroom
600 gal / day
5-bedroom
750 gal / day
6-bedroom
900 gal / day
1 - 5 160 200 260 340 400
6 - 15 200 300 400 500 600
16 - 30 300 400 500 600 700
31 - 45 400 500 600 800 900
46 - 60 500 600 700 900 1,100

Alternative Option for Increased Rock Usage...

Depth of gravel Reduction in trench
12 20 %
18 33 %
24 40 %

Alternative Option for Use of Absorption Bed...

Percolation rate (min / inch) Area / Bedroom (ft2) Loading rate (gal / ft2 . day)
1 - 5 300 0.500
6 - 15 400 0.375
16 - 30 600 0.250

Construction Details (All Soil Absorption Trenches)...

Depth : Lateral trenches shall not exceed 36 inches in depth unless authorized by the administrative authority, but a more shallow trench bottom depth of 18 to 24 inches is recommended. Not less than 6 inches of porous soil shall be provided over the laterals. Minimum separation between trench bottom and groundwater, rock formation or other confining layers shall be 36 inches even if extra rock is used under the pipe.
Length : No lateral absorption trench shall be greater than 100 feet long.
Separation distance : At least 6 feet of undisturbed soil shall be left between each trench edge on level sites. The steeper the slope of the ground, the greater the separation distance should be. Two feet of separation distance should be added for each 5 percent increase in slope from level.
Grade : Trench bottom should be constructed level from end to end. On sloping ground, the trench shall follow a uniform land contour to maintain a minimum soil cover of 6 inches while ensuring a level trench bottom.
Compaction : There shall be minimum use or traffic of heavy equipment on the area proposed for soil absorption. In addition, it is prohibited to use heavy equipment on the bottom of the trenches in the absorption area.
Fill soil : Soil absorption systems shall not be installed in fill soil. Disturbed soils which have stabilized for at least one year would require a recent percolation test.
Bearing strength : Soil absorption systems shall be designed to carry loadings to meet AASHTO H-10 standards.
Soil smearing : Soils with significant clay content should not be worked when wet. If soil moisture causes sidewall smearing, the trench bottom and sidewalls shall be scarified.

Gravel Systems...

Gravel : A minimum of 6 inches of clean, washed river gravel, free of clay and clay coatings, shall be laid below the distribution pipe, and enough gravel shall be used to cover the pipe. This gravel shall be of such a size that 100 percent will pass a 2½-inch screen and 100 percent will be retained on a ¾-inch screen. Limestone or crushed rock is not recommended for soil absorption systems. If used it shall meet the following criteria ; (a) Abrasion loss : The percent wear, as determined in accordance with the AASHTO T 96, Grading C, shall not exceed 40 percent. (b) Freeze and thaw loss : When subjected to the freezing and thawing test, Iowa DOT Materials Laboratory Test Method 211, Method A, the percentage loss shall not exceed 10 percent. (c) Absorption : The percent absorption, determined in accordance with Iowa DOT Materials Laboratory Test Method 202, shall not exceed 3 percent. (d) Gradation : The aggregate shall have not more than 1.5 percent by weight pass a No. 16 sieve.
Trench width : Lateral trenches for gravel systems shall be a minimum of 24 inches and a maximum of 36 inches in width at the bottom of the trench.
Grade : The distribution pipes shall be laid with a minimum grade of 2 inches per 100 feet of run and a maximum grade of 6 inches per 100 feet of run, with a preference given to the lesser slope.
Pipe : Distribution pipe shall be PVC rigid plastic meeting ASTM Standard 2729, or other suitable material approved by the administrative authority. The inside diameter shall be not less than 4 inches, with perforations at least 1/2inch and no more than % inch in diameter spaced no more than 40 inches apart. Two rows of perforations shall be provided located 120 degrees apart along the bottom half of the tubing (each 60 degrees up from the bottom centerline). The end of the pipe in each trench shall be sealed with a watertight cap unless, on a level site, a rooter is installed connecting the trenches together. Coiled perforated plastic pipe shall not be used when installing absorption systems.
Gravel cover : Unbacked, rolled, 3½-inch-thick fiberglass insulation, untreated building paper, synthetic drainage fabric, or other approved material shall be laid so as to separate the gravel from the soil backfill.

Gravelless Pipe Systems...

Application : Gravelless subsurface absorption systems may be used as an alternative to conventional 4-inch pipe placed in gravel-filled trenches. However, they cannot be used in areas where conventional systems would not be allowed due to poor permeability, high groundwater, or insufficient depth to bedrock.
Installation : Manufacturer's specifications and installation procedures shall be adhered to.
Material : The 8 and 10-inch I.D. corrugated polyethylene tubing used in gravelless systems shall meet the requirements of ASTM F667, Standard Specification for Large Diameter Corrugated Polyethylene Tubing.
Perforations : Two rows of perforations shall be located 120 degrees apart along the bottom half of the tubing (each 60 degrees up from the bottom centerline). Perforations shall be cleanly cut into each inner corrugation along the length of the tubing and should be staggered so that there is only one hole in each corrugation.
Top marking : The tubing should be visibly marked to indicate the top of the pipe.
Filter wrap : All gravelless drainfield pipe shall be encased, at the point of manufacture, with a geotextile filter wrap specific to this purpose.
Trench width : If dug with a backhoe, the minimum trench width for the gravelless system shall be 18 inches in sandy loam soil to ensure proper backfill around the bottom half of the pipe. In clay soils, the minimum trench width shall be 24 inches. If the pipe is laid in with a wheel trencher leaving a curved trench bottom, the trench width may be just 2 inches wider than the outside diameter of the pipe.
Length of trench : The total length of absorption trench for a 10-inch gravelless tubing installation shall be the same as given in table given above for a conventional absorption trench except for fine sandy soils. An increase of at least 20 percent in total trench length shall be required if 8-inch tubing is used rather than 10 inch.

Chamber Systems...

Application : Chamber systems may be used as an alternative to conventional 4 inch pipe placed in gravel-filled trenches. However, they cannot be used in areas where conventional systems would not be allowed due to poor permeability, high groundwater, or insufficient depth to bedrock.
Installation : Manufacturer's specifications and installation procedures shall be closely adhered to.
Length of trench : The total length of absorption trench for chambers 24 inches or less in bottom width shall be the same as given in table given above for a conventional absorption trench. For chambers greater than 33 inches in width a reduction of 25 percent from the lengths given in table given above may be used.
Sidewall : The chambers shall have at least 6 inches of sidewall effluent soil exposure height.

Gravity Distribution...

On a hillside : Septic tank effluent may be serially loaded to the soil absorption trenches by drop boxes or overflow piping (rigid sewer pipe). Otherwise, effluent shall be distributed evenly to all trenches by use of a distribution box or commercial distribution regulator approved by the administrative authority.
Design : When a distribution box is used, it shall be of proper design and installed with separate watertight headers leading from the distribution box to each lateral. Header pipes shall be rigid PVC plastic pipe meeting ASTM Standard 2729 or equivalent.
Outlets height : The distribution box shall have outlets at the same level at least 4 inches above the bottom, of the box to provide a minimum of 4 inches of water retention in the box.
Baffles : There shall be a pipe tee or baffle at the inlet to break the water flow.
Unused outlets : All unused outlet holes in the box shall be securely closed.
Interior coating : All distribution boxes shall be constructed of corrosion resistant rigid plastic materials, or other corrosion-resistant material approved by the administrative authority.
Outlets level : All outlets of the distribution box shall be made level. A 4-inch cap with an offset hole approximately 2½ inches in diameter shall be installed on each outlet pipe. These caps shall be rotated until all outlets discharge at the same elevation. Equivalent leveling devices may be approved by the local authority.
Equal length required : The soil absorption area serviced by each outlet of the distribution box shall be equal.

Dosing Systems...

Pump Systems...

Pump and pit requirements : In the event the effluent from the septic tank outlet cannot be discharged by gravity and still maintain proper lateral depths, the effluent shall discharge into a watertight vented pump pit with an inside diameter of not less than 24 inches, equipped with a tight manhole cover at grade level. The sump vent shall extend a minimum of 6 inches above grade level and shall be a minimum size of 1¼ inches fitted with a return bend. The pump shall be of a submersible type of corrosion-resistant material.
Pump setting : The pump shall be installed in the pump pit in a manner that ensures ease of service and protection from frost and settled sludge. The pump shall be set to provide a dosing frequency of approximately twice a day based on the maximum design flow. No on-site electrical connections shall be made in the pump pit. These connections shall be made in an exterior weatherproof box.
Pressure line size : The pressure line from the pump to the point of discharge shall not be smaller than the outlet of the pump it serves.
Drainage : Pressure lines shall be installed to provide total drainage between dosings to prevent freezing or be buried below frost level up to the distribution box.
High water alarm : Pump pits shall be equipped with a sensor set to detect if the water level rises above the design high water level when the pump fails. This sensor shall activate an auditory or visual alarm to alert the homeowner that repairs are required.
Discharge point : The effluent shall discharge under pressure into a distribution box or may be distributed by small diameter pipes throughout the entire absorption field.

Dosing Siphons...

Dosing siphons may also be used. Manufacturer's specifications shall be adhered to for installation. Similar dosing volumes and frequencies are recommended. Dosing siphons require periodic cleaning to ensure their continued proper operation.

Mound System...

General Requirements...

(a) Mound systems shall be permitted only after a thorough site evaluation has been made and landscaping, dwelling placement, effect on surface drainage and general topography have been considered.
(b) Mound systems shall not be utilized on sites which are subject to flooding with a ten-year or greater frequency.
(c) Mound systems shall not be utilized on soils where the high groundwater level, impermeable bedrock or soil strata having a percolation rate exceeding 120 minutes per inch occur within 12 inches of natural grade, or where creviced bedrock occurs within 20 inches of natural grade.
(d) Mound systems shall be constructed only upon undisturbed naturally occurring soils.
(e) Mound systems shall be located in accordance with the distances specified in the first able as measured from the outer edge of the mound.
(f) No buildings, driveways or other surface or subsurface obstructions shall be permitted within 50 feet on the down gradient side of the mound when the mound is constructed on a slope greater than 5 percent. No future construction shall be permitted in this effluent disposal area as long as the mound is in use.
(g) Specifications given in these rules for mounds are minimal and may not be sufficient for all applications. Technical specifications are changing with experience and research. Other design information beyond the scope of these rules may be necessary to properly design a mound system.

Material for Mound Fill...

(a) The mound shall be constructed using clean, medium-textured sand, sometimes referred to as concrete sand. The sand size shall be such that at least 25 percent by weight shall have a diameter between 2.0 and 0.25 mm, less than 35 percent, with a diameter between 0.25 and 0.05 mm and less than 5 percent with a diameter between 0.002 and 0.05 mm.
(b) Rock Fragments larger than 1/16 inch (2.0 mm) shall not exceed 15 percent by weight of the material used for sandy fill.

Construction Details...

(a) There shall be a minimum of 3 feet of fill material and undisturbed naturally occurring soils between the bottom of the washed gravel and the highest elevation of the limiting conditions.
(b) Gravel shall be washed and shall range in size from ¾ inch to 2½ inches.
(c) From 1 to 2 feet of medium-textured sand (depending upon the underlying soil depth) must be placed between the bottom of the gravel and the top of the plowed surface of the naturally occurring soil.
(d) Mound systems shall utilize absorption bed distribution piping design. The bed shall be installed with the long dimension parallel to the land contour. Systems on steep slopes with slowly permeable soils should be narrow to reduce the possibility of toe seepage.
(e) Minimum spacing between distribution pipes shall be 4 feet, and a minimum of 3 feet shall be maintained between any trench and the sidewall of the mound.
(f) No soil under or up to 50 feet down gradient of the mound may be removed or disturbed except as specified herein.
(g) Construction equipment which would cause undesirable compaction of the soil shall be kept off the base area. Construction or plowing shall not be initiated when the soil moisture content is high. If a sample of soil from approximately 9 inches below the surface can be easily rolled into a 1/8 to ¼-inch diameter wire, the soil moisture content is too high for construction purposes.
(h) Aboveground vegetation shall be closely cut and removed from the ground surface throughout the area to be utilized for the placement of the fill material.
(i) The area shall be plowed to a depth of 7 to 8 inches, parallel to the land contour with the plow throwing the soil up slope to provide a proper interface between the fill and the natural soil. Tree stumps should be cut flush with the surface of the ground, and roots should not be pulled.
(j) The base area of the mound is to be calculated on the results of percolation rate. The base area of the mound below and downslope from the trenches, excluding the area under the end slopes, must be large enough for the natural soil to absorb the estimated daily wastewater flow.
(k) The area of the fill material shall be sufficient to extend 3 feet beyond the edge of the gravel area before the sides are shaped to at least a 4:1 slope (preferably 5: 1).
(l) Distribution system : (1) The distribution pipe shall be rigid plastic pipe, schedule 40 or 80 with 1 -inch nominal diameter. (2) The distribution pipe shall be provided with a single row of ¼-inch perforations in a straight fine 30 inches on center along the length of the pipe or an equivalent design that ensures uniform distribution. All joints and connections shall be solvent-cemented. (3) The distribution pipe shall be placed in the clean, washed gravel (or crushed limestone with holes downward. The gravel shall be a minimum of 9 inches in depth below and 3 inches in depth above the pipe. (4) No perforations shall be permitted within 3 inches of the outer ends of any distribution pipes. (5) The outer ends of all pressure distribution lines shall be securely capped. (6) The central pressure manifold should consist of 1½-inch or 2-inch solid plastic pipe using a tee or cross for connecting the distribution lines.
(m) Construction should be initiated immediately after preparation of the soil interface by placing all of the sandy fill material needed for the mound (to the top of the trench) to a minimum depth of 21 inches above the plowed surface. This depth will permit excavation of the trenches to accommodate the 9 inches of washed gravel or crushed stone necessary for the distribution piping.
(n) The absorption trench or trenches shall be hand excavated to a depth of 9 inches, the bottoms of the trenches made certain to be level.
(o) Twelve inches of gravel shall be placed in the trench and hand leveled, and then remove 3 inches of the gravel removed with a shovel in the location where the distribution pipe will be placed. After the distribution pipe is placed the pipe shall be covered with 2 inches of gravel.
(p) The top of the gravel shall be covered with synthetic drainage fabric. Unbacked, rolled 31/2-inch-thick fiberglass insulation, untreated building paper, or other suitable material may be used with approval of the administrative authority. Plastic or treated building paper shall not be used.
(r) After installation of the distribution system, gravel and material over the gravel, the entire mound is to be covered with topsoil native to the site or of similar characteristics to support vegetation found in the area. The entire mound shall be crowned by providing- 12 inches of topsoil on the side slopes with a minimum of 18 inches over the center of the mound. The entire mound shall be seeded, sodded or otherwise provided with a grass cover to ensure stability of the installation.
(s) The area surrounding the mound shall be graded to provide for diversion of surface runoff water.

Dosing...

(a) Dosing shall be required for mound systems.
(b) The dosing volume shall be five to ten times the distribution piping network volume.
(c) The size of the dosing pump or siphon shall be capable of maintaining an approximate pressure of one psi at the outer ends of the distribution lines.

Drip Irrigation...

General Design...

Pretreatment required : These systems must be preceded by a secondary treatment system discharging a treated, filtered effluent with BOD and TSS values less than 20 mg / L.
Separation from groundwater : Drip irrigation systems shall have a minimum vertical separation distance to high groundwater level or bedrock of 20 inches.
Maximum hillside slope : Drip irrigation systems shall not be installed on slopes of more than 25 percent.
Other info : Specifications given in these rules for drip irrigation are al and may not be sufficient for all applications. Technical specifications are changing with experience and research. Other design information beyond the scope of these rules may be necessary to properly design a drip irrigation system.

Emitter Layout...

Discharge rate : Systems shall be designed so that emitters, discharge approximately 1 gpm at 12 psi or other rates suggested by the manufacturer and approved by the administrative authority.
Grid size : Drip lines shall be run in parallel lines 2 feet apart. Emitters shall be placed in the drip lines on 2-foot intervals with emitters offset 1 foot between adjacent lines. Each emitter shall cover 4 square feet of absorption area.
Field size : The field shall be sized according to the application rate given in table shown below.
Depth of drip lines : Drip lines shall be laid on the contour 6 to 12 inches deep with a maximum line length of 100 feet. Lines may be of unequal length.
Interconnection : Drip lines shall all be connected to supply and return headers such that the entire system will automatically drain back to the dosing tank or pump pit upon completion of the pumping cycle. Vacuum breakers shall be positioned at the high point of the supply and return headers. The dosing tank shall have a high water audio/visual alarm.

Length of Drip Line Required Per Bedroom...

Percolation rate
(min / inches)
Design hydraulic loading
(gpd / ft2)
Length of drip line
(feet / bedroom)
1 - 5 2.0 40
6 - 15 1.3 60
16 - 30 0.9 90
31 - 45 0.6 150
46 - 60 0.4 200
61 - 90 0.2 400
91 - 120 0.1 800