Mechanical and Electrical Design of Pumping Stations - 18...
Chapter - 18 : Station and Equipment Grounding...
18-1. General...
Following are the recommended practices for system and
equipment grounding in pumping stations. However,
special applications may require variations to the recommended
practices. A thorough discussion of grounding
principles can be found in ANSI/IEEE 142, Recommended
Practices for Grounding of Industrial and Commercial
Power Systems. Installations should also comply
with the applicable provisions of Article 250 - Grounding
of the National Electric Code (NFPA-70). Typical
grounding plans are shown on Plates 21 and 22.
18-2. Station and Equipment Grounding...
( a ) General.
An effective grounding system is an
essential part of a pump station electrical system. In
general, 19-millimeter (3/4-inch) by 6-meter (20-foot)
ground rods should be driven at the corners of the structure
and exothermically joined to a ground bus run completely
around the periphery of the pumping station. The
ground bus should be installed a minimum of 0.5 meter
(18 inches) outside the building wall and a minimum of
0.8 meter (30 inches) below the finished grade. Additional
lengths or numbers of ground rods should be
added as required to achieve a maximum resistance to
ground of 25 ohms. In rocky ground where driven rods
are impractical, it is sometimes more economical and
desirable to use a grid system with cable spacings of
approximately 3 meters (10 feet) being common. The
cables should be placed 150 millimeters (6 inches) to
300 millimeters (1 foot) deep and encased in concrete.
( b ) Grounding conductors.
At least four grounding
conductors should be run from the ground bus or grid
and exothermically welded to a ground loop embedded in
the operating floor. All connections to either the ground
loop or ground bus should be by exothermic welds.
( c ) Ground bus.
The ground bus should be exothermically
connected to the sump floor rebars, any steel
columns of the structure, and metallic underground water
piping where present.
( d ) Sizing of grounding bus and loop conductors.
Sizing of grounding bus and loop conductors should be
made in accordance with the applicable requirements of
the National Electrical Code (NFPA-70). For mechanical
strength, however, the grounding conductors should not be smaller than No. 2/0-AWG conductor. However, it
may be desirable to exceed these values where exceptional
precaution is required or where extremely high
ground-fault currents are expected.
( e ) Frames and enclosures.
The frames of stationary
or permanently located motors, and the frames and enclosures
of static equipment such as transformers should be
grounded by direct connection to the operating floor
ground loop through an equipment grounding conductor
equal in size to the largest conductor in the line connected
to the equipment, but in general not less than
No. 6 AWG. The equipment grounding conductors shall
be connected to the equipment through the use of a
clamp-type connector.
( f ) Switchgear.
To provide a convenient method of
grounding switchgear, a ground bus should be provided
as part of the equipment. The switchgear ground bus
must not be smaller in current-carrying capacity than
25 percent of the highest continuous-current rating of any
piece of primary apparatus to which it is connected. The
switchgear ground bus should, in turn, be connected to
the operating floor ground loop by conductors having a
current-carrying capacity equal to that of the switchgear
ground bus.
( g ) Other noncurrent carrying metal.
All other noncurrent
carrying metal such as ladders, fences, fuelstorage
tanks, etc., shall be connected to either the
ground bus or operating floor ground loop. All neutral
conductors of grounded power supplies shall be solidly
grounded to the station ground system.
( h ) Utility power.
The utility furnishing power to the
station should be contacted to determine if any interconnections
are required between the pumping station ground
grid and the substation ground grid.
18-3. System Grounding...
( a ) General.
The basic reasons for system grounding are the following :
(1) To limit the difference of electric potential between all uninsulated conducting objects in a local area.
(2) To provide for isolation of faulted equipment and circuits when a fault occurs.
(3) To limit overvoltage appearing on the system under various conditions.
( b ) Low-voltage systems.
It is recommended that
pumping stations with electrical systems of 1,000 volts
and below be solidly grounded. Solid grounding is the
least expensive way to detect and selectively isolate
ground fault through the usage of fast-acting ground-fault
relaying. However, use of a solidly grounded lowvoltage
distribution system increases the probability of
damage from arcing ground faults. The driving voltage
of these systems tends to sustain arcs rather than clear
them through the standard phase overcurrent protective
devices. High impedances associated with the arc may
limit fault current to levels too low for detection by
conventional over-current protective devices. For this
reason, sensitive ground-fault relaying should be provided
on the feeders and the main of all solidly grounded systems.
Ungrounded operation of low-voltage systems is
not recommended because of the potential over-voltage
problems.
( c ) Medium-voltage systems.
Modern power systems
in this range of voltages are usually low-resistance
grounded to limit the damage due to ground faults in the
windings of rotating machines and yet permit sufficient
fault current for the detection and selective isolation of
individually faulted circuits. The lowest ground-fault
current (highest resistance) consistent with adequate
ground relay sensitivity should be used. High-resistance
grounding is not recommended for medium-voltage
systems.