Mechanical and Electrical Design of Pumping Stations - 19...
Chapter - 19 : Surge Protection...
19-1. General...
( a ) Lightning-induced voltage surges.
Pumping stations
are particularly vulnerable to lightning-induced
voltage surges on incoming power lines, since it is characteristic
of their operation to be in use during thunderstorms.
Therefore, special care should be taken to reduce
the magnitude of these voltage surges to avoid major
damage to the electrical equipment contained within. A
relatively small investment can greatly reduce the voltage
stresses imposed on rotating machinery and switchgear
by lightning-induced surges.
( b ) Protective equipment.
There are two transient
elements of a voltage surge that require different protective
equipment. The protection of the major insulation to
ground is accomplished by station surge arresters which
limit the amplitude or reflections of the applied impulse
waves within the motor windings. The protection of turn
insulation by reducing the steepness of wave fronts
applied to or reflected within the motor windings is
accomplished by protective capacitors.
19-2. Medium-Voltage Motors...
To obtain the most reliable protection of the motor’s
major and turn insulation systems, a set of arresters and
capacitors should be installed as close as possible to the
motor terminals. The arresters should be valve-type, Station-Class designed for rotating machine protection.
The capacitors should be of the non-PCB type. The
leads from the phase conductor to the capacitor and from
the capacitor to ground should be as short as possible.
(If solid state motor controllers are used, the addition of
capacitors at the motor terminals may not be recommended.
Chopped-wave equipment such as SCR controlled
motor starters can generate surges and harmonics.
The capacitors can contribute to the problem by increasing
resonance effects. The manufacturer should be consulted
for the particular application.)
19-3. Low-Voltage Motors...
Motors of 600 volts and below have relatively higher
dielectric strength than medium-voltage machines. Normally,
when higher speed motors of this voltage class are
connected through a transformer protected by Station-
Class arresters on the primary side, no additional protection
is warranted. However, due to the more expensive
slower speed motors employed in pump stations, plus the
critical nature of these motors, the minimal additional
cost of lightning protection is justified. A three-phase
valve-type low voltage arrester should be provided at the
service entrance to the station and a three-phase capacitor
should be provided at each motor terminal.
19-4. Substation...
The utility should be requested to supply valve-type
Station-Class surge arresters on the primary side of the
substation transformer.