Mechanical and Electrical Design of Pumping Stations - 23...
Chapter - 23 : Station Studies...
23-1. Voltage Drop Studies...
( a ) General.
A preliminary voltage drop study for
motor start-up as well as for motor-running conditions
should be made during the initial design phase. The final
study should be made during the approval drawing and
data review phase of the project. The voltage drop study
must be updated whenever the electrical system is
revised. Computer programs are available to calculate
the system’s voltage dips and currents from motor starting
to full load speed. For further information on voltage
studies, refer to ANSI/IEEE 141, Recommended Practice
for Electric Power Distribution for Industrial Plants and
ANSI/IEEE 339, Power System Analysis.
( b ) Motor start-up.
Motor start-up voltage drop
depends on the motor inrush current. Depending upon
the method of motor start-up, the inrush current ranges
from two to six times the motor full-load current. Excessive
starting voltage drop can result in problems such as
motor stalling, nuisance tripping of undervoltage relays,
motor overload devices, and temporary dips in lighting
system brightness or restriking of high-intensity discharge
lamps. During motor starting, the voltage level at the
motor terminals should be maintained at approximately
80 percent of rated voltage or higher as recommended by
the motor manufacturer.
( c ) Motor running.
Undervoltage during the motor
running condition may produce excessive heating in the
motor windings, nuisance tripping of undervoltage relays
and motor-overload devices, dim lighting, and reduced
output of electric space heating equipment. Approximately
5-percent voltage drop from the transformer secondary
terminals to the load terminals is acceptable.
23-2. System Protection and Coordination Studies...
( a ) General.
When a short circuit occurs in the electrical
system, overcurrent protective devices such as
circuit breakers, fuses, and relays must operate in a predetermined,
coordinated manner to protect the faulted
portion of the circuit while not affecting the power flow
to the rest of the system.
(1) Isolation of faulted section. Isolation of the
faulted section protects the electrical system from severe
damage. It also results in efficient trouble shooting since the faulted section is downstream of the tripped protective
device. Efficient troubleshooting results in reduction
of costly repair time and system downtime.
(2) One-line diagram of electrical system. A oneline
drawing of the electrical system is an important
element of the protection and coordination study. The
one-line diagram is discussed in detail in
paragraph 23-3c.
( b ) Procedures.
The coordination study is accomplished
by overlaying protective device characteristic
curves over equipment damage curves. This method is
applicable in the range of fault clearing times greater
than approximately 0.016 seconds (1 cycle) on a 60-Hz
basis. For clearing times faster than this, as is the case
for protecting solid state inverters, protection and coordination
studies are achieved by comparing let-through
energy (I-squared-t) values of current-limiting fuses
(CLFs) to withstand energy values of the equipment
being protected. Similarly, coordination between CLFs is
achieved by comparing values of let-through energy of
upstream fuses with the values of the melting energy of
the downstream fuses.
(1) Protection and coordination study. A protection
and coordination study may be performed manually or
with the aid of a computer. Computer software is available
with pre-programmed time-current characteristic
curves. The result of the computer study can be automatically
drawn onto standard time-current characteristic
paper by the computer printer.
(2) Additional information. For further information on protection and coordination studies refer to :
(a) ANSI/IEEE 141, Recommended Practice for Electric Power Distribution for Industrial Plants.
(b) ANSI/IEEE 242, Recommended Practices for Protection and Coordination of Industrial and Commercial Power Systems.
( c ) Main disconnecting device.
The utility supplying
the power to the facility should be consulted regarding
the type of protective device it recommends on the load
side of the supply line which best coordinates with the
source side protective device furnished by the utility.
( d ) Motors.
Protective device characteristics must be
coordinated with motor start-up characteristics. The
devices must be insensitive enough to allow motors to
start up without nuisance tripping caused by the relatively high magnitude of motor start-up current. The devices
must be sensitive enough, however, to operate during
overload or short-circuit conditions.
( e ) Transformers.
Transformer protection is similar
to that of motor protection as discussed above. The
protective device must be insensitive to the transformer
magnetizing in-rush current, but sensitive enough to operate
for a short circuit condition. Note, the new ANSI
standard on transformer protection (ANSI/IEEE C57.109)
could be used as an alternative to the classic method of
transformer protection. Transformer magnetizing inrush
should be specified as 8 X full-load current for transformers
rated less than 3 MVA, and 12 X full-load current,
otherwise.
( f ) Cables.
Cable protection requires coordinating
the protective device characteristics with the insulation
smolder characteristics of the power cable. The insulation
smolder characteristics of the cable are the same as
the "short-circuit withstand" and "short-circuit heating
limits" of the cable.
( g ) Specification requirements.
The pump station
construction specifications should require the contractor
to furnish the completed protection and coordination
study during the shop drawing approval process. The
study should then be reviewed by the designer and
returned to the contractor with any appropriate comments.
It should be clearly stated in the specifications
that it is the contractor’s responsibility to coordinate with
his various equipment suppliers to produce a complete
and accurate protection and coordination study. The
actual preparation of the study should be performed by
the equipment manufacturer or an independent consultant.
The construction specifications should require the contractor
to submit the following items as one complete
submittal :
(1) Full-size reproducibles of protective device characteristic curves.
(2) The motor-starting characteristics in the form of time versus current curves or data points.
(3) Data indicating the short-circuit withstand capability of motor control centers, panelboards, switchgear, safety
switches, motor starters, and bus bar and interrupting capacities of circuit breakers and fuses.
(4) Transformer impedance data. These data should be submitted in one of three forms: percent IR and percent IX, percent
IZ with X/R ratio, or percent IZ with no load and total watt losses.
(5) Cable insulation smolder temperature.
(6) Completed time-current coordination curves indicating equipment damage curves and device protection characteristics.
(7) A marked-up one-line diagram indicating ratings and trip sizing of all equipment.
23-3. Short-Circuit Studies...
( a ) General.
Short-circuit calculations are necessary
in order to specify equipment withstand ratings and for
use in conjunction with the protective device coordination
study. Switchgear, motor control centers, safety
switches, panelboards, motor starters, and bus bar must
be capable of withstanding available fault currents. After
the available fault current has been calculated at each bus
in the electrical network, the available fault current withstand
ratings are specified.
(1) Circuit breakers. Circuit breakers must be capable
of withstanding the mechanical and thermal stresses
caused by the available fault currents. They must be able
to remain closed even though tremendous forces are
present in such a direction as to try to force the breaker
contacts open. The ability of circuit breakers to remain
closed is indicated by their momentary ratings. The
momentary rating is a function of the circuit breakers
interrupting rating, which is the ability to interrupt a fault
current without incurring excessive damage to the
breaker.
(2) Fuses. Fuses must also be capable of safely
interrupting fault current and are rated in terms of interrupting
capacity.
(3) Motor starters. Motor starters furnished with
motor circuit protectors are available with short-circuit
withstand ratings up to 100,000 amperes. Starters furnished
with fusible switches are available with withstand
ratings up to 200,000 amperes.
( b ) Procedures.
The basic elements of a short-circuit
study are the short-circuit calculations and the one-line
diagram of the electrical system. For pumping stations
the three-phase bolted fault is usually the only fault condition
that is studied. Utility systems line-to-ground
faults can possibly range to 125 percent of the three-phase value, but in pumping plants line-to-ground
fault currents of greater magnitude than the three-phase
value are rare. Line-to-line fault currents are approximately
87 percent of the three-phase fault current.
(1) Preliminary short-circuit study. A preliminary
short-circuit study should be prepared during the design
phase of the project. The final study should be prepared
by the pump station construction contractor as described
below.
(2) Calculations. The magnitude of the fault currents
can be calculated using long-hand methods. However,
software is available to reduce preparation time and
simplify the task for large complex systems.
(3) Additional information. For further information on short circuit studies refer to : (a) ANSI/IEEE 141, Recommended Practice for Electric Power Distribution for Industrial Plants. (b) ANSI/IEEE 242, Recommended Practices for Protection and
Coordination of Industrial and Commercial Power Systems.
( c ) One-line diagram.
Plate 13 indicates the format
of the one-line diagram developed as part of the preliminary
and final protection and coordination and shortcircuit
studies. Plates 15 and 16 are typical of one-line
diagrams to be issued with the plans and specifications.
(1) Standard symbols. Standard symbols for use on
the one-line diagram are listed in ANSI Y32.2. Any
nonstandard symbols that are used to show special features
or equipment should be explained in the drawing
legend to make their meaning entirely clear.
(2) Check list. The following is a check list of
items that should be included on the study one-line
diagram:
(a) Fault current. This is the available three-phase
fault current of the utility supply at the pumping station
metering point. This information can be presented in
amperes, MVA, or as an impedance to the utility infinite
bus (impedance in ohms or per unit on a specified base).
The designer should also request the utility to provide an
estimate of future three-phase fault levels. The estimate
provides an indication of utility system changes which
may affect the future short-circuit interrupting capability
and withstand ratings of installed electrical equipment.
(b) Bus voltage.
(c) Transformers. The diagram should show winding
connections, KVA rating, percent impedance, the X/R
ratio, neutral grounding, if any, including the neutral
ground impedance value, if not solidly grounded.
(d) Power cables. The diagram should show size,
length, conductor material, whether single or multiconductor,
and whether the cable is carried in a magnetic
or nonmagnetic duct.
(e) Circuit breakers. The diagram should show type
by appropriate symbol (for example, molded case or
draw-out) and the following ampere ratings: interrupting
rating, frame size, thermal trip setting, and magnetic trip
setting. It should show also the range of adjustment of
the magnetic trip, if adjustable, as well as the recommended
setting as determined by a protective device
coordination study.
(f) Switches and fuses. The diagram should show
type of fuse or switch and the continuous and interrupting
rating in amperes.
(g) Motors. The following should be given: horsepower
or kilowatt rating, power factor, synchronous or
induction type, mechanical speed (revolutions per minute),
and subtransient reactance. The following additional
data are required for synchronous machines:
transient reactance, synchronous reactance, and the
impedance of any grounding resistor.
(h) Location(s) where power purchased from a utility company is metered.
(i) The following information is required for preparation
of the protection and coordination study: locations
of potential and current transformers and relays and
metering. Show location, quantity, and types of relays
by standard IEEE device numbers, such as 51 for overcurrent
relays, 67 for directional overcurrent relays.
Device numbers are listed in ANSI/IEEE C37.2.
( d ) Specification requirements.
The pump station
construction specifications should require the contractor
to furnish the final short-circuit study during the shop
drawing approval process. The study should then be
reviewed by the designer and returned to the contractor
with any appropriate comments. It should be clear in the
specifications that it is the contractor’s responsibility to
coordinate with his various equipment suppliers to produce a complete and accurate short-circuit study. The
actual preparation of the study should be performed by
the equipment manufacturer or an independent consultant.
The specifications must state that the cable sizes, ampere
ratings of the protective devices, and the short-circuit
withstand ratings of the equipment shown on the one-line
diagram are preliminary and that the contractor shall
furnish a complete and final one-line diagram upon completion
of the coordination and protection and shortcircuit
studies.